(I)IoT Security News
News, Vulnerabilities

Advantech WebAccess/SCADA

1. EXECUTIVE SUMMARY

2. RISK EVALUATION

Successful exploitation of these vulnerabilities may allow information disclosure, deletion of files, and remote code execution.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of WebAccess/SCADA, a SCADA software platform, are affected:

3.2 VULNERABILITY OVERVIEW

3.2.1    IMPROPER LIMITATION OF A PATHNAME TO A RESTRICTED DIRECTORY (‘PATH TRAVERSAL’) CWE-22

A path traversal vulnerability is caused by a lack of proper validation of a user-supplied path prior to use in file operations. An attacker can leverage this vulnerability to delete files while posing as an administrator.

CVE-2019-10985 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H)

3.2.2    STACK-BASED BUFFER OVERFLOW CWE-121

Multiple stack-based buffer overflow vulnerabilities are caused by a lack of proper validation of the length of user-supplied data. Exploitation of these vulnerabilities may allow remote code execution.

CVE-2019-10991 has been assigned to these vulnerabilities. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.3    HEAP-BASED BUFFER OVERFLOW CWE-122

Multiple heap-based buffer overflow vulnerabilities are caused by a lack of proper validation of the length of user-supplied data. Exploitation of these vulnerabilities may allow remote code execution.

CVE-2019-10989 has been assigned to these vulnerabilities. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.4    OUT-OF-BOUNDS READ CWE-125

An out-of-bounds read vulnerability is caused by a lack of proper validation of user-supplied data. Exploitation of this vulnerability may allow disclosure of information.

CVE-2019-10983 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N).

3.2.5    OUT-OF-BOUNDS WRITE CWE-787

Multiple out-of-bounds write vulnerabilities are caused by a lack of proper validation of the length of user-supplied data. Exploitation of these vulnerabilities may allow remote code execution.

CVE-2019-10987 has been assigned to these vulnerabilities. A CVSS v3 base score of 8.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.2.6    UNTRUSTED POINTER DEREFERENCE CWE-822

Multiple untrusted pointer dereference vulnerabilities may allow a remote attacker to execute arbitrary code.

CVE-2019-10993 has been assigned to these vulnerabilities. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H)

3.3 BACKGROUND

3.4 RESEARCHER

Mat Powell, Natnael Samson (@NattiSamson) and EljahLG, working with Trend Micro’s Zero Day Initiative (ZDI), reported these vulnerabilities to NCCIC.

4. MITIGATIONS

Advantech has released Version 8.4.1 of WebAccess/SCADA to address the reported vulnerabilities. Users can download the latest version of WebAccess/SCADA at the following location (registration required):

https://support.advantech.com/support/DownloadSRDetail_New.aspx?SR_ID=1-MS9MJV&Doc_Source=Download

NCCIC recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should:

NCCIC reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

NCCIC also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Additional mitigation guidance and recommended practices are publicly available on the ICS-CERT website in the Technical Information Paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to NCCIC for tracking and correlation against other incidents.

NCCIC also recommends that users take the following measures to protect themselves from social engineering attacks:

No known public exploits specifically target these vulnerabilities.

 

Source:

https://www.us-cert.gov/ics/advisories/icsa-19-178-05

 