https://www.cisa.gov/news-events/ics-advisories/icsa-24-303-03

https://www.cisa.gov/news-events/ics-advisories/icsa-24-303-03

1. EXECUTIVE SUMMARY

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow an unauthenticated attacker to remotely execute arbitrary code.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of InfraSuite Device Master, a real-time device monitoring software, are affected:

3.2 Vulnerability Overview

3.2.1 DESERIALIZATION OF UNTRUSTED DATA CWE-502

Delta Electronics InfraSuite Device Master versions prior to 1.0.12 are affected by a deserialization vulnerability that targets the Device-Gateway, which could allow deserialization of arbitrary .NET objects prior to authentication, resulting in remote code execution.

CVE-2024-10456 has been assigned to this vulnerability. A CVSS v3.1 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-10456. A base score of 9.3 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

3.4 RESEARCHER

Simon Humbert of Trend Micro reported this vulnerability to CISA.

4. MITIGATIONS

Delta Electronics states that this issue was fixed by version 1.0.13 released in October 2024. Delta recommends updating to version 1.0.13 or later.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

Source:

https://www.cisa.gov/news-events/ics-advisories/icsa-24-303-03

Related posts

Rockwell Automation FactoryTalk Linx

(I) IoT
4 years ago

Philips Alice 6 Vulnerabilities (Update A)

(I) IoT
6 years ago

Malware Analysis Report (AR19-304A) MAR-10135536-8 – North Korean Trojan: HOPLIGHT

(I) IoT
5 years ago
Exit mobile version