(I)IoT Security News
ICS, News, Vulnerabilities

OSIsoft PI Vision

OSIsoft PI Vision

1. EXECUTIVE SUMMARY

2. RISK EVALUATION

Successful exploitation of these vulnerabilities may allow a remote attacker with write access to the PI ProcessBook files to inject code that is imported into PI Vision, or disclose information to a user with insufficient privileges.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

All versions prior to PI Vision 2020 are affected.

3.2 VULNERABILITY OVERVIEW

3.2.1    IMPROPER NEUTRALIZATION OF INPUT DURING WEB PAGE GENERATION (‘CROSS-SITE SCRIPTING’) CWE-79

A remote attacker with write access to PI ProcessBook files could inject code that is imported into PI Vision. Unauthorized information disclosure, modification, or deletion is also possible if a victim views or interacts with the infected display. This vulnerability affects PI System data and other data accessible with victim’s user permissions.

CVE-2020-25163 has been assigned to this vulnerability. A CVSS v3 base score of 7.7 has been assigned; the CVSS vector string is (AV:N/AC:H/PR:L/UI:R/S:C/C:H/I:H/A:N).

3.2.2    INCORRECT AUTHORIZATION CWE-863

PI Vision could disclose information to a user with insufficient privileges for an AF attribute.

CVE-2020-25167 has been assigned to this vulnerability. A CVSS v3 base score of 4.9 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:N/A:N).

3.3 BACKGROUND

3.4 RESEARCHER

OSIsoft reported these vulnerabilities to CISA.

4. MITIGATIONS

OSIsoft released PI Vision 2020 Version 3.5.0, which resolves these vulnerabilities.

Recommended defensive measures and related configuration settings are described on the OSIsoft customer portal (Login required).

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should:

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on us-cert.cisa.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.cisa.gov in the Technical Information Paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks: 

No known public exploits specifically target these vulnerabilities.

Source:

https://us-cert.cisa.gov/ics/advisories/icsa-20-315-02