(I)IoT Security News
ICS, News, Vulnerabilities

Rockwell Automation FactoryTalk Services Platform

Rockwell Automation FactoryTalk Services Platform

1. EXECUTIVE SUMMARY

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow an unauthenticated attacker to execute remote COM objects with elevated privileges.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

All versions of FactoryTalk Services Platform are affected.

3.2 VULNERABILITY OVERVIEW

3.2.1    IMPROPER INPUT VALIDATION CWE-20

The affected product’s redundancy host service (RdcyHost.exe) does not validate supplied identifiers, which could allow an unauthenticated, adjacent attacker to execute remote COM objects with elevated privileges. 

CVE-2020-12033 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (AV:A/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.3 BACKGROUND

3.4 RESEARCHER

4. MITIGATIONS

Affected users are encouraged to use Rockwell Automation Knowledgebase article 25612 to determine if FactoryTalk Services Platform is installed. Those using the affected product are directed to implement a secure communication strategy as outlined in Rockwell Automation Knowledgebase article 109056.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should:

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on us-cert.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.gov in the Technical Information Paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.

No known public exploits specifically target this vulnerability. 

Source:

https://www.us-cert.gov/ics/advisories/icsa-20-170-04