(I)IoT Security News
ICS, News, Vulnerabilities

Siemens KTK, SIDOOR, SIMATIC, and SINAMICS (Update A)

Siemens KTK, SIDOOR, SIMATIC, and SINAMICS

1. EXECUTIVE SUMMARY

2. UPDATE INFORMATION

This updated advisory is a follow-up to the original advisory titled ICSA-20-105-08 Siemens KTK, SIDOOR, SIMATIC, and SINAMICS that was published April 14, 2020, on the ICS webpage on us-cert.gov. 

3. RISK EVALUATION

Successful exploitation of this vulnerability could create a denial-of-service condition.

4. TECHNICAL DETAILS

4.1 AFFECTED PRODUCTS

The following Siemens products are affected:

——— Begin Update A Part 1 of 1 ———

——— End Update A Part 1 of 1 ———

4.2 VULNERABILITY OVERVIEW

4.2.1    UNCONTROLLED RESOURCE CONSUMPTION (‘RESOURCE EXHAUSTION’) CWE-400

The Interniche-based TCP stack can be forced to make resource intense calls for every incoming packet, which can lead to a denial of service.

CVE-2019-19300 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

4.3 BACKGROUND

4.4 RESEARCHER

Siemens reported this vulnerability to CISA.

5. MITIGATIONS

Siemens recommends applying updates if available:

Siemens has not identified any specific mitigations or workarounds and recommends following their general security recommendations. As a general security measure, Siemens strongly recommends protecting network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends configuring the environment according to the Siemens operational guidelines for Industrial Security and following the recommendations in the product manuals.For additional information, please refer to Siemens Security Advisory SSA-593272

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should:

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on us-cert.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.gov in the Technical Information Paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.

No known public exploits specifically target this vulnerability.

Source:

https://www.us-cert.gov/ics/advisories/icsa-20-105-08

Related posts

Baxter ExactaMix (Update A)

(I) IoT
4 years ago

Siemens CP1604 and CP1616

(I) IoT
5 years ago

Mitsubishi Electric MELSEC

(I) IoT
4 years ago
Exit mobile version