(I)IoT Security News
Critical vulnerabiliities, ICS, Industrial IoT (IIoT), IoT Security, Market, News

Siemens SIMATIC Cloud Connect 7

1. EXECUTIVE SUMMARY

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow an attacker to execute arbitrary code. 

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following products from Siemens are affected: 

3.2 VULNERABILITY OVERVIEW

3.2.1 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN A COMMAND (‘COMMAND INJECTION’) CWE-77 

The web-based management of affected devices does not properly validate user input, making it susceptible to command injection. This could allow an authenticated privileged remote attacker to execute arbitrary code with root privileges. 

CVE-2023-28832 has been assigned to this vulnerability. A CVSS v3 base score of 7.2 has been assigned. The CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H). 

3.2.2 USE OF HARD-CODED PASSWORD CWE-259 

The affected device uses a hard-coded password to protect the diagnostic files. This could allow an authenticated attacker to access protected data. 

CVE-2023-29103 has been assigned to this vulnerability. A CVSS v3 base score of 4.3 has been assigned. The CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:L/I:N/A:N). 

3.2.3 IMPROPER LIMITATION OF A PATHNAME TO A RESTRICTED DIRECTORY (‘PATH TRAVERSAL’) CWE-22 

The filename in the upload feature of the web-based management of the affected device is susceptible to a path traversal vulnerability. This could allow an authenticated privileged remote attacker to overwrite any file the Linux user `ccuser` has write access to, or to download any file the Linux user `ccuser` has read-only access to. 

CVE-2023-29104 has been assigned to this vulnerability. A CVSS v3 base score of 6.0 has been assigned. The CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:L/I:L/A:H). 

3.2.4 MISSING STANDARDIZED ERROR HANDLING MECHANISM CWE-544 

The affected device is vulnerable to a denial-of-service condition while parsing a random (non-JSON) MQTT payload. This could allow an attacker who can manipulate the communication between the MQTT broker and the affected device to cause a denial-of-service condition. 

CVE-2023-29105 has been assigned to this vulnerability. A CVSS v3 base score of 5.9 has been assigned. The CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H). 

3.2.5 EXPOSURE OF SENSITIVE INFORMATION TO AN UNAUTHORIZED ACTOR CWE-200 

The export endpoint is accessible via REST application programming interface (API) without authentication. This could allow an unauthenticated remote attacker to download the files available via the endpoint. 

CVE-2023-29106 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been assigned. The CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N). 

3.2.6 FILES OR DIRECTORIES ACCESSIBLE TO EXTERNAL PARTIES CWE-552 

The export endpoint discloses some undocumented files. This could allow an unauthenticated remote attacker to gain access to additional information resources. 

CVE-2023-29107 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been assigned. The CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N). 

3.2.7 IMPROPER LIMITATION OF A PATHNAME TO A RESTRICTED DIRECTORY (‘PATH TRAVERSAL’) CWE-22 

The filename in the upload feature of the web-based management of the affected device is susceptible to a path traversal vulnerability. This could allow an authenticated privileged remote attacker to write any file with the extension `.db`. 

CVE-2023-29128 has been assigned to this vulnerability. A CVSS v3 base score of 3.8 has been assigned. The CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:N/I:L/A:L). 

3.3 BACKGROUND

3.4 RESEARCHER

Siemens reported these vulnerabilities to CISA. 

4. MITIGATIONS

Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk: 

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals. 

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage

For further inquiries on security vulnerabilities in Siemens products, users should contact the Siemens ProductCERT

For more information, see the associated Siemens security advisory SSA-555292 in HTML and CSAF

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities. Specifically, users should: 

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. 

CISA also provides a section for control systems security recommended practices on the ICS webpage at cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies

Source:
https://www.cisa.gov/news-events/ics-advisories/icsa-23-131-04