(I)IoT Security News
ICS, News, Vulnerabilities

Synergy Systems & Solutions HUSKY RTU (Update A)

Synergy Systems & Solutions HUSKY RTU

1. EXECUTIVE SUMMARY

——— Begin Update A Part 1 of 3 ———

——— End Update A Part 1 of 3 ———

2. UPDATE INFORMATION

This updated advisory is a follow-up to the original advisory titled ICSA-20-042-01 Synergy Systems & Solutions HUSKY RTU that was published February 11, 2020, to the ICS webpage on us-cert.gov.

3. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow an attacker to read sensitive information, execute arbitrary code, or cause a denial-of-service condition.

4. TECHNICAL DETAILS

4.1 AFFECTED PRODUCTS

The following versions of HUSKY RTU, a remote terminal unit, are affected:

4.2 VULNERABILITY OVERVIEW

4.2.1    IMPROPER AUTHENTICATION CWE-287

The affected product does not require adequate authentication, which may allow an attacker to read sensitive information or execute arbitrary code.

CVE-2019-20046 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

4.2.2    IMPROPER INPUT VALIDATION CWE-20

Specially crafted malicious packets could cause disconnection of active authentic connections or reboot of device.

CVE-2019-20045 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

——— Begin Update A Part 2 of 3 ———

4.2.3    MISSING AUTHENTICATION FOR CRITICAL FUNCTION CWE-306

The affected product does not require authentication for TELNET access, which may allow an attacker to change configuration or perform other malicious activities.

CVE-2019-16879 has been assigned to this vulnerability. A CVSS v3 base score of 9.3 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:C/C:L/I:N/A:H).

4.2.4    IMPROPER CHECK FOR UNUSUAL OR EXCEPTIONAL CONDITIONS CWE-754

The affected product is vulnerable to specially crafted TCP packets, which can cause the device to shut down or reboot and lose configuration settings.

CVE-2020-7800 has been assigned to this vulnerability. A CVSS v3 base score of 9.3 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:C/C:L/I:N/A:H).

4.2.5    EXPOSURE OF SENSITIVE INFORMATION TO AN UNAUTHORIZED ACTOR CWE-200

The affected product is vulnerable to information exposure over the SNMP protocol.

CVE-2020-7801 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:N).

4.2.6    INCORRECT DEFAULT PERMISSIONS CWE-276

The affected product is vulnerable to insufficient default permissions, which could allow an attacker to view network configurations through SNMP communication.

CVE-2020-7802 has been assigned to this vulnerability. A CVSS v3 base score of 9.3 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:C/C:L/I:H/A:N).

——— End Update A Part 2 of 3 ———

4.3 BACKGROUND

4.4 RESEARCHER

The VAPT Team, C3i Center, IITK, UP, India, reported to CISA that they had coordinated these vulnerabilities directly with SSS.

5. MITIGATIONS

SSS makes the following recommendations to mitigate risk.

——— Begin Update A Part 3 of 3 ———

For more information, see the associated SSS security bulletin.

——— End Update A Part 3 of 3 ———

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on us-cert.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.gov in the Technical Information Paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.

No known public exploits specifically target these vulnerabilities.

Source:

https://www.us-cert.gov/ics/advisories/icsa-20-042-01

Related posts

Cracked Windows installations are serially infected with EternalBlue exploit code

(I) IoT
6 years ago

Systemd flaw could cause the crash or hijack of vulnerable Linux machines

(I) IoT
6 years ago

Z-Wave Downgrade Attack Left Over 100 Million IoT Devices Open to Hackers

IoT
7 years ago
Exit mobile version