(I)IoT Security News
News, Vulnerabilities

WIBU SYSTEMS AG WibuKey Digital Rights Management (Update C)

1. EXECUTIVE SUMMARY

2. UPDATE INFORMATION

This updated advisory is a follow-up to the advisory update titled ICSA-19-043-03 Siemens Licensing Software for SICAM 230 (Update B) that was published March 13, 2019, on the NCCIC/ICS-CERT website.

3. RISK EVALUATION

Successful exploitation of these vulnerabilities may allow information disclosure, privilege escalation, or remote code execution.

4. TECHNICAL DETAILS

4.1 AFFECTED PRODUCTS

The following products are affected by vulnerabilities in WibuKey Digital Rights Management (DRM):

——— Begin Update C Part 1 of 2 ———
——— End Update C Part 1 of 2 ———

.2 VULNERABILITY OVERVIEW

4.2.1    INFORMATION EXPOSURE CWE-200

A specially crafted IRP (I/O request packet) can cause the driver to return uninitialized memory, which may result in kernel memory disclosure.

CVE-2018-3989 has been assigned to this vulnerability. A CVSS v3 base score of 4.3 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:N/S:C/C:L/I:N/A:N).

4.2.2    OUT-OF-BOUNDS WRITE CWE-787

A specially crafted IRP (I/O request packet) can cause a buffer overflow resulting in kernel memory corruption, which may allow privilege escalation.

CVE-2018-3990 has been assigned to this vulnerability. A CVSS v3 base score of 9.3 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H).

4.2.3    HEAP-BASED BUFFER OVERFLOW CWE-122

A specially crafted TCP packet sent to Port 22347/TCP can cause a heap overflow, which may lead to remote code execution.

CVE-2018-3991 has been assigned to this vulnerability. A CVSS v3 base score of 10.0 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H).

4.3 BACKGROUND

4.4 RESEARCHER

Siemens and BSI Germany reported these vulnerabilities to NCCIC.

5. MITIGATIONS

Updated Wibu Systems Software can be found at the following link:

https://www.wibu.com/support/user/downloads-user-software.html

5.1    SIEMENS

——— Begin Update C Part 2 of 2 ———

Siemens has released the following updates for WinCC OA which address the WibuKey vulnerabilities:

v3.14-P025 (https://www.winccoa.com/downloads/category/patches-315-16.html)

v3.15-P018 (https://www.winccoa.com/downloads/category/patches-315-17.html)

v3.16-P007 (https://www.winccoa.com/downloads/category/patches-316-1.html)

WinCC OA users can also apply the solutions below to resolve the vulnerabilities.

——— End Update C Part 2 of 2 ———

Siemens recommends users upgrade to WibuKey DRM Version 6.50 or newer for all affected Siemens products. Siemens also recommends mitigating CVE-2018-3991 by blocking Port 22347/TCP. For detailed information, see Siemens security advisories SSA-760124 and SSA-844562 at the following link:

http://www.siemens.com/cert/en/cert-security-advisories.htm

5.2    COPA-DATA

COPA-DATA recommends users upgrade WibuKey DRM to Version 6.50a or newer, restrict physical and network access, segment network traffic, ensure systems using WibuKey WkLAN Server are not external facing, and apply application whitelisting. For detailed information, see COPA_DATA’s security advisory at the following link:

https://www.copadata.com/fileadmin/user_upload/faq/files/CD_SVA_2019_1.pdf

5.3    SPRECHER AUTOMATION

Sprecher Automation recommends users upgrade WibuKey DRM to Version 6.50b or newer, restrict physical and network access, segment network traffic, ensure systems using WibuKey WkLAN Server are not external facing, and apply application whitelisting. For detailed information, see Sprecher Automation’s security advisory at the following link:

https://www.sprecher-automation.com/fileadmin/kundendaten/teaser/News/2018/SPRECON-V460_Security_Vulnerability_Announcement_2019-01_Issue_1.pdf

5.4    PHOENIX CONTACT

Phoenix Contact has calculated different CVSS vectors from those in the Vulnerability Overview section. See the Phoenix Contact or CERT@VDE advisory for details.

Phoenix Contact recommends those using dongle-based licensing to update to WibuKey Version 6.50 or newer. MEVIEW3 Versions 3.14.25 and 3.15.18 will include Version 6.50 of WibuKey. For those using hardware code-based licensing, Phoenix Contact recommends removing the WibuKey application. For detailed information, the Phoenix Contact MEVIEW3 security advisory can be found at the following link:

https://www.phoenixcontact.com/psirt

CERT@VDE has also published an advisory for the Phoenix Contact MEVIEW3 at the following link:

https://cert.vde.com/de-de/advisories/vde-2019-003

5.5    NCCIC

NCCIC recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should:

NCCIC reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

NCCIC also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Additional mitigation guidance and recommended practices are publicly available on the ICS-CERT website in the Technical Information Paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to NCCIC for tracking and correlation against other incidents.

NCCIC also recommends that users take the following measures to protect themselves from social engineering attacks:

 

Source:

https://ics-cert.us-cert.gov/advisories/ICSA-19-043-03

 