(I)IoT Security News
ICS, News, Vulnerabilities

Schneider Electric Modicon M221 Programmable Logic Controller

Schneider Electric Modicon M221

1. EXECUTIVE SUMMARY

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow an attacker to take control over the PLC and gain unauthorized access, which could result in exposure of sensitive information.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Schneider Electric reports these vulnerabilities affect the following Modicon products:

3.2 VULNERABILITY OVERVIEW

3.2.1    INADEQUATE ENCRYPTION STRENGTH CWE-326

An inadequate encryption strength vulnerability exists that could allow the attacker to break the encryption key when the attacker has captured the traffic between EcoStruxure Machine – Basic software and Modicon M221 controller.

CVE-2020-7565 has been assigned to this vulnerability. A CVSS v3 base score of 7.1 has been calculated; the CVSS vector string is (AV:A/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.2.2    SMALL SPACE OF RANDOM VALUES CWE-334

A small space of random values vulnerability exists that could allow the attacker to break the encryption keys when the attacker has captured the traffic between EcoStruxure Machine – Basic software and Modicon M221 controller.

CVE-2020-7566 has been assigned to this vulnerability. A CVSS v3 base score of 7.1 has been calculated; the CVSS vector string is (AV:A/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.2.3    MISSING ENCRYPTION OF SENSITIVE DATA CWE-311

A missing encryption of sensitive data vulnerability exists that could allow the attacker to find the password hash when the attacker has captured the traffic between EcoStruxure Machine – Basic software and Modicon M221 controller and has broken the encryption keys.

CVE-2020-7567 has been assigned to this vulnerability. A CVSS v3 base score of 7.1 has been calculated; the CVSS vector string is (AV:A/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.2.4    EXPOSURE OF SENSITIVE INFORMATION CWE-200

An exposure of sensitive information to an unauthorized actor vulnerability exists that could allow non-sensitive information disclosure when the attacker has captured the traffic between EcoStruxure Machine – Basic software and Modicon M221 controller.

CVE-2020-7568 has been assigned to this vulnerability. A CVSS v3 base score of 3.1 has been calculated; the CVSS vector string is (AV:A/AC:H/PR:N/UI:N/S:U/C:L/I:N/A:N).

3.2.5    USE OF A ONE-WAY HASH WITH A PREDICTABLE SALT CWE-760

A use of a one-way hash with a predictable salt vulnerability exists that could allow the attacker to pre-compute the hash value using a dictionary attack, effectively disabling the protection that an unpredictable salt would provide.

CVE-2020-28214 has been assigned to this vulnerability. A CVSS v3 base score of 3.3 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:L/UI:N/S:U/C:L/I:N/A:N).

3.3 BACKGROUND

3.4 RESEARCHER

Yehuda Anikster and Rei Henigman of Claroty, and Seok Min Lim and Bryon Kaan of Trustwave reported these vulnerabilities to Schneider Electric.

4. MITIGATIONS

Schneider Electric recommends users to apply the following mitigations to help reduce the risk of exploit:

Schneider Electric strongly recommends following industry cybersecurity best practices:

Refer to Schneider Electric’s security bulletin SEVD-2020-315-05 for specific mitigation details.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on us-cert.cisa.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.cisa.gov in the Technical Information Paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks: 

No known public exploits specifically target these vulnerabilities. High skill level is needed to exploit.

Source:

https://us-cert.cisa.gov/ics/advisories/icsa-20-343-04

Related posts

Geutebrück GmbH E2 Series IP Cameras

(I) IoT
5 years ago

New Spectre attack enables secrets to be leaked over a network

(I) IoT
6 years ago

Siemens SIMATIC S7 (Update A)

(I) IoT
4 years ago
Exit mobile version