(I)IoT Security News
ICS, News, Vulnerabilities

Schneider Electric SoMachine Basic

Schneider Electric SoMachine Basic

1. EXECUTIVE SUMMARY

2. RISK EVALUATION

Successful exploitation of this vulnerability may result in disclosure and retrieval of arbitrary data on the affected node via out-of-band (OOB) attack.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Schneider Electric reports this vulnerability affects the following SoMachine Basic: 

3.2 VULNERABILITY OVERVIEW

3.2.1    IMPROPER RESTRICTION OF XML EXTERNAL ENTITY REFERENCE CWE-611

Schneider Electric SoMachine Basic prior to v1.6 SP1 suffers from an XML External Entity (XXE) vulnerability using the DTD parameter entities technique resulting in disclosure and retrieval of arbitrary data on the affected node via out-of-band (OOB) attack. This vulnerability is triggered when input passed to the xml parser is not sanitized while parsing the xml project/template file. 

CVE-2018-7783 has been assigned to this vulnerability. A CVSS v3 base score of 8.6 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:C/C:H/I:H/A:H).

3.3 BACKGROUND

3.4 RESEARCHER

Gjoko Krstikj of Applied Risk reported this vulnerability to Schneider Electric.

4. MITIGATIONS

Schneider Electric has replaced SoMachine Basic with EcoStruxure Machine Expert – Basic. The following steps are recommended for mitigation of this issue:
STEP 1: Update software and firmware 

STEP 2: Update projects in EcoStruxure Machine Expert – Basic

STEP 3: Transfer applications. 

Please see Schneider Electric’s publication SEVD-2018-142-01 for more information.

Schneider Electric also recommends the following general security practices:

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on us-cert.cisa.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.cisa.gov in the Technical Information Paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.

No known public exploits specifically target this vulnerability. 

Source:

https://us-cert.cisa.gov/ics/advisories/icsa-21-103-01

Related posts

AVEVA Historian Web Server

(I) IoT
3 months ago

NUUO NVRmini2 and NVRsolo

(I) IoT
6 years ago

OpenClinic GA

(I) IoT
4 years ago
Exit mobile version