Siemens S7-300/400 PLC Vulnerabilities (Update E)

SIMATIC S7-300 and SIMATIC S7-400

1. EXECUTIVE SUMMARY

2. UPDATE INFORMATION

This updated advisory is a follow-up to the advisory update titled ICSA-16-348-05 SIEMENS S7-300/400 PLC Vulnerabilities (Update D) that was published January 25, 2018, to the ICS webpage on us-cert.gov.

3. RISK EVALUATION

Successful exploitation of these vulnerabilities could lead to a denial-of-service condition or result in credential disclosure.

4. TECHNICAL DETAILS

4.1 AFFECTED PRODUCTS

The following products are affected:

——— Begin Update E Part 1 of 1 ———

4.2 VULNERABILITY OVERVIEW

4.2.1    INFORMATION EXPOSURE CWE-200

An attacker with network access to Port 102/TCP (ISO-TSAP) or via Profibus could obtain credentials from the PLC if Protection-Level 2 is configured on the affected devices.

CVE-2016-9159 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N).

4.2.2    IMPROPER INPUT VALIDATION CWE-20

Specially crafted packets sent to Port 80/TCP could cause the affected devices to go into defect mode. A cold restart is required to recover the system.

CVE-2016-9158 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N).

——— End Update E Part 1 of 1 ———

4.3 BACKGROUND

4.4 RESEARCHER

Zhu WenZhe from Beijing Acorn Network Technology reported these vulnerabilities to CISA.

5. MITIGATIONS

Siemens provides the following firmware versions to resolve CVE-2016-9158:

Siemens also recommends the following mitigations:

Siemens strongly recommends users protect network access with appropriate mechanisms (e.g., firewalls, segmentation, VPN). Siemens also advises that users configure the operational environment according to Siemens’ Operational Guidelines for Industrial Security.

For more information on these vulnerabilities and more detailed mitigation instructions, please see Siemens Security Advisory SSA-731239.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should:

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on us-cert.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.gov in the Technical Information Paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.

No known public exploits specifically target these vulnerabilities.

Source:

https://www.us-cert.gov/ics/advisories/ICSA-16-348-05