(I)IoT Security News
ICS, News, Vulnerabilities

Siemens SCALANCE S-600 (Update B)

Siemens SCALANCE S-600

1. EXECUTIVE SUMMARY

2. UPDATE INFORMATION

This updated advisory is a follow-up to the advisory update titled ICSA-20-042-10 Siemens SCALANCE S-600 (Update A) that was published August 11, 2020 to the ICS webpage on us-cert.cisa.gov. 

3. RISK EVALUATION

These vulnerabilities could allow a remote attacker to conduct denial-of-service or cross-site scripting attacks. User interaction is required for a successful exploitation of the cross-site-scripting attack.

4. TECHNICAL DETAILS

4.1 AFFECTED PRODUCTS

The following versions of SCALANCE S-600, are affected:

——— Begin Update B Part 1 of 2 ———

——— End Update B Part 1 of 2 ———

4.2 VULNERABILITY OVERVIEW

4.2.1    CROSS-SITE SCRIPTING CWE-80

The integrated configuration web server of the affected devices could allow cross-site scripting (XSS) attacks if unsuspecting users are tricked into accessing a malicious link.

CVE-2019-6585 has been assigned to this vulnerability. A CVSS v3 base score of 4.7 has been calculated; the CVSS vector string is (AV:N/AC:H/PR:N/UI:R/S:C/C:L/I:L/A:N).

4.2.2    UNCONTROLLED RESOURCE CONSUMPTION CWE-400

Specially crafted packets sent to Port 443/TCP of affected devices could cause a denial-of-service condition of the web server.

CVE-2019-13925 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

4.2.3    UNCONTROLLED RESOURCE CONSUMPTION CWE-400

Specially crafted packets sent to Port 443/TCP of affected devices could cause a denial-of-service condition of the web server. A cold reboot is required to restore the functionality of the device.

CVE-2019-13926 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

4.3 BACKGROUND

4.4 RESEARCHER

Melih Berk Ekşioğlu reported some of these vulnerabilities to Siemens.

5. MITIGATIONS

Siemens has identified the following specific workarounds and mitigations that customers can apply to reduce the risk: 

——— Begin Update B Part 2 of 2 ———

——— End Update B Part 2 of 2 ———

For more information on these vulnerabilities and associated software updates, please see Siemens security advisory SSA-591405

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities. Specifically, users should take the following measures to protect themselves from social engineering attacks: 

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on us-cert.cisa.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.cisa.gov in the Technical Information Paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.

No known public exploits specifically target these vulnerabilities.

Source:

https://us-cert.cisa.gov/ics/advisories/icsa-20-042-10

Related posts

How Will Artificial Intelligence Impact IoT in 2018

(I)IoT
7 years ago

Cisco IOS XR Software for ASR 9000 Series Aggregation Services Routers PPPoE Denial of Service Vulnerability

(I) IoT
8 months ago

Siemens SIMATIC S7-1200 and S7-1500 CPU Families

(I) IoT
3 years ago
Exit mobile version