(I)IoT Security News
ICS, IoT Security, News, Vulnerabilities

Viessmann Climate Solutions SE Vitogate 300

Viessmann Climate Solutions SE Vitogate 300Viessmann Climate Solutions SE Vitogate 300

Viessmann Climate Solutions SE Vitogate 300

1. EXECUTIVE SUMMARY

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow an attacker to achieve remote code execution.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of Viessmann Climate Solutions SE Vitogate 300, a solution to connecting boilers and heat pumps to a building management system, are affected:

3.2 Vulnerability Overview

3.2.1 Use of Hard-coded Credentials CWE-798

In Viessmann Vitogate 300 versions 2.1.3.0 and prior there is a vulnerability that affects the function isValidUser of the file /cgi-bin/vitogate.cgi of the component Web Management Interface. The manipulation leads to use of hard-coded password.

CVE-2023-5222 has been assigned to this vulnerability. A CVSS v3.1 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2023-5222. A base score of 9.3 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.2 Direct Request (‘Forced Browsing’) CWE-425

In Viessmann Vitogate 300 versions 2.1.3.0 and prior there is a vulnerability in some unknown functionality of the file /cgi-bin/. The manipulation leads to direct request.

CVE-2023-5702 has been assigned to this vulnerability. A CVSS v3.1 base score of 6.5 has been calculated; the CVSS vector string is (AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N).

A CVSS v4 score has also been calculated for CVE-2023-5702. A base score of 7.1 has been calculated; the CVSS vector string is (CVSS4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N).

3.2.3 Improper Neutralization of Special Elements used in a Command (‘Command Injection’) CWE-77

In Viessman Vitogate 300 versions 2.1.3.0 and prior, /cgi-bin/vitogate.cgi allows an unauthenticated attacker to bypass authentication and execute arbitrary commands via shell metacharacters in the ipaddr params JSON data for the put method.

CVE-2023-45852 has been assigned to this vulnerability. A CVSS v3.1 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2023-45852. A base score of 9.3 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

CISA discovered a public Proof of Concept (PoC) as authored by ByteHunter and reported it to Viessmann.

4. MITIGATIONS

Viessmann Climate Solutions SE recommends customers update to version 3.0.0.0 to fix these vulnerabilities. The software is available to download at their (website)

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.

5. UPDATE HISTORY

This product is provided subject to this Notification and this Privacy & Use policy.

Source:

https://www.cisa.gov/news-events/ics-advisories/icsa-24-254-01

Related posts

Siemens Energy PLUSCONTROL 1st Gen

(I) IoT
3 years ago

Weintek EasyWeb cMT

(I) IoT
3 years ago

CISCO Identity Services Engine Unauthorized File Access Vulnerability

IoT
2 years ago
Exit mobile version