1. EXECUTIVE SUMMARY
-
CVSS v3 8.2
- ATTENTION: Exploitable remotely/low skill level to exploit
- Vendor: Siemens
- Equipment: SIMATIC
- Vulnerabilities: Improper restriction of XML external entity reference
2. UPDATE INFORMATION
This updated advisory is a follow-up to the updated advisory titled ICSA-17-243-01 Siemens industrial products using the Discovery Service of the OPC UA protocol stack by the OPC foundation (Update B) that was published November 30, 2017, on the NCCIC/ICS-CERT website.
3. RISK EVALUATION
Successful exploitation of this vulnerability may allow an attacker to access various resources.
4. TECHNICAL DETAILS
4.1 AFFECTED PRODUCTS
Siemens reports that the vulnerability affects the following industrial products, which use the Discovery Service of the OPC UA protocol stack by the OPC foundation:
- SIMATIC IT Production Suite: Versions between v6.5 and v7.1
- SIMATIC NET PC Software: All versions prior to 13.2
- SIMATIC PCS 7: v8.0 and v8.1
- SIMATIC WinCC: All versions prior to v7.2
- SIMATIC WinCC Runtime Professional:
- v13: All versions
- v14: All versions prior to v14 SP1
4.2 VULNERABILITY OVERVIEW
4.2.1 IMPROPER RESTRICTION OF XML EXTERNAL ENTITY REFERENCE (‘XXE’) CWE-611
By sending specially crafted packets to the OPC Discovery Server at Port 4840/TCP, an attacker may be able to cause the system to access various resources chosen by the attacker.
CVE-2017-12069 has been assigned to this vulnerability. A CVSS v3 base score of 8.2 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:H).
4.3 BACKGROUND
- CRITICAL INFRASTRUCTURE SECTORS: Chemical, Energy, Food and Agriculture, Water and Wastewater Systems
- COUNTRIES/AREAS DEPLOYED: Worldwide
- COMPANY HEADQUARTERS LOCATION: Germany
4.4 RESEARCHER
Sergey Temnikov of Kaspersky Lab reported this vulnerability to Siemens.
5. MITIGATIONS
Siemens provides fixes for the following products and recommends users upgrade to the newest version:
- SIMATIC IT Production Suite:
Contact local support to update to v7.1
- SIMATIC NET PC Software: Update to version 15 SP1
https://support.industry.siemens.com/cs/ww/en/view/109762690
- SIMATIC WinCC Runtime Professional: Update to v14 SP1
https://support.industry.siemens.com/cs/ww/en/view/109746276
Siemens has identified the following specific workarounds and mitigations that customers can apply to reduce the risk:
- Operating the devices only within trusted networks.
- Turn off the discovery service after commissioning or block it on the local firewall: https://support.industry.siemens.com/cs/ww/en/view/109749461
- Apply cell protection concept,
- Use VPN for protecting network communication between cells, and
- Apply defense in depth.
Siemens recommends users protect network access with appropriate mechanisms such as firewalls, segmentation, and VPNs. Siemens also advises that users configure the operational environment according to Siemens’ Operational Guidelines for Industrial Security:
https://www.siemens.com/cert/operational-guidelines-industrial-security
For more information on this vulnerability and more detailed mitigation instructions, please see Siemens Security Advisory SSA-535640 at the following location:
http://www.siemens.com/cert/advisories
The OPC Foundation also published a security bulletin for this vulnerability:
NCCIC reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
NCCIC also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Additional mitigation guidance and recommended practices are publicly available on the ICS-CERT website in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to NCCIC for tracking and correlation against other incidents.
No known public exploits specifically target this vulnerability.
Source:
https://ics-cert.us-cert.gov/advisories/ICSA-17-243-01-0
Stay connected