1. EXECUTIVE SUMMARY
-
CVSS v3 5.3
- ATTENTION: Exploitable from an adjacent network
- Vendor: Siemens
- Equipment: SIMATIC, SINUMERIK, and PROFINET IO
- Vulnerability: Improper Input Validation
2. UPDATE INFORMATION
This updated advisory is a follow-up to the original advisory titled ICSA-18-079-02 Siemens SIMATIC, SINUMERIK, and PROFINET IO that was published March 20, 2018, on the NCCIC/ICS-CERT website.
3. RISK EVALUATION
Successful exploitation of this vulnerability could result in a denial-of-service condition requiring a manual restart to recover the system.
4. TECHNICAL DETAILS
4.1 AFFECTED PRODUCTS
Siemens reports that the vulnerability affects the following products:
- SIMATIC CP 343-1 Advanced: All versions,
- SIMATIC CP 343-1 Standard: All versions,
- SIMATIC CP 443-1 Advanced: All versions,
- SIMATIC CP 443-1 Standard: All versions,
- SIMATIC S7-1500 Software Controller incl. F: All versions prior to v1.7.0,
- SIMATIC S7-1500 incl. F: All versions prior to v1.7.0,
- SIMATIC S7-300 incl. F and T: All versions,
- SIMATIC S7-400 H v6: All versions,
- SIMATIC S7-400 PN/DP v6 Incl. F: All versions prior to v6.0.7,
- SIMATIC S7-400 PN/DP v7 Incl. F: All versions,
- SIMATIC S7-410: All versions prior to v8.1,
- SIMATIC WinAC RTX 2010 incl. F: All versions,
- SINUMERIK 828D: All versions prior to v4.7 SP6 HF1, and
- Softnet PROFINET IO for PC-based Windows systems: All versions.
4.2 VULNERABILITY OVERVIEW
4.2.1 IMPROPER INPUT VALIDATION CWE-20
Responding to a PROFINET DCP request with a specially crafted PROFINET DCP packet could result in a denial-of-service condition of the requesting system. This vulnerability could be exploited if the attacker is located on the same Ethernet segment (OSI Layer 2) as the targeted device.
CVE-2018-4843 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been calculated; the CVSS vector string is (AV:A/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H).
4.3 BACKGROUND
- CRITICAL INFRASTRUCTURE SECTORS: Chemical, Critical Manufacturing, Energy, Food and Agriculture, Water and Wastewater Systems.
- COUNTRIES/AREAS DEPLOYED: Worldwide
- COMPANY HEADQUARTERS LOCATION: Germany
4.4 RESEARCHER
Siemens ProductCERT reported this vulnerability to NCCIC.
5. MITIGATIONS
Siemens has provided the following updates for mitigations:
- SIMATIC S7-1500 Software Controller incl. F: Update to v1.8.5 or newer, which can be located here:
https://support.industry.siemens.com/cs/ww/en/view/109478528
- SIMATIC S7-1500 incl. F: Update to v1.8.5 or newer, which can be located here:
https://support.industry.siemens.com/cs/ww/en/view/109478459
- SIMATIC S7-400 PN/DP V6 Incl. F: Update to v6.0.7, which can be located here:
https://support.industry.siemens.com/cs/ww/en/view/109474874
- SIMATIC S7-410: Update to v8.1, which can be located here:
https://support.industry.siemens.com/cs/ww/en/view/109476571
- SINUMERIK 828D: Update to v4.7 SP6 HF1 SINUMERIK software can be obtained from the local Siemens account manager.
For all other affected products, Siemens has identified the following specific workarounds and mitigations that users can apply to reduce the risk, refer to:
- Apply cell protection concept.
- Use VPN for protecting network communication between cells.
- Apply defense-in-depth.
Additional information is available at:
https://www.siemens.com/cert/operational-guidelines-industrial-security
As a general security measure, Siemens strongly recommends protecting network access to devices with appropriate mechanisms. In order to run the devices in a protected IT environment, Siemens particularly recommends configuring the environment according to Siemens’ operational guidelines for industrial security, and following the recommendations in the product manuals. Additional information on industrial security by Siemens can be found at:
https://www.siemens.com/industrialsecurity
For more information on this vulnerability and associated software updates, please see Siemens security notification SSA-592007 on their website:
https://www.siemens.com/cert/advisories
NCCIC recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should:
- Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet.
- Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
- When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
NCCIC reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
NCCIC also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Additional mitigation guidance and recommended practices are publicly available on the ICS-CERT website in the Technical Information Paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to NCCIC for tracking and correlation against other incidents.
No known public exploits specifically target this vulnerability. High skill level is needed to exploit.
Source:
https://ics-cert.us-cert.gov/advisories/ICSA-18-079-02
Stay connected