1. EXECUTIVE SUMMARY

  • CVSS v3 7.8
  • ATTENTION: Low skill level to exploit
  • Vendor: Siemens
  • Equipment: TIA Portal
  • Vulnerability: Path Traversal

2. UPDATE INFORMATION

This updated advisory is a follow-up to the advisory update titled ICSA-20-014-05 Siemens TIA Portal (Update A) that was published April 14, 2020, to the ICS webpage on us-cert.gov.

3. RISK EVALUATION

Successful exploitation of this vulnerability could allow a local attacker to execute arbitrary code with SYSTEM privileges.

4. TECHNICAL DETAILS

4.1 AFFECTED PRODUCTS

The following versions of TIA Portal, the Totally Integrated Automation Portal, are affected:

——— Begin Update B Part 1 of 2 ———

  • TIA Portal v14: All versions prior to v14 SP1 Update 10

——— End Update B Part 1 of 2 ———

  • TIA Portal v15: All versions prior to v15.1 Upd 4
  • TIA Portal v16: All versions prior to v16 Upd 1

4.2 VULNERABILITY OVERVIEW

4.2.1    IMPROPER LIMITATION OF A PATHNAME TO A RESTRICTED DIRECTORY (‘PATH TRAVERSAL’) CWE-22

Changing the contents of a configuration file could allow an attacker to execute arbitrary code with SYSTEM privileges. This vulnerability could be exploited by an attacker with a valid account and limited access rights on the system. No user interaction is required.

CVE-2019-10934 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

4.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Chemical, Critical Manufacturing, Energy, Food and Agriculture, Water and Wastewater Systems
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

4.4 RESEARCHER

\William Knowles from Applied Risk reported this vulnerability to Siemens.

5. MITIGATIONS

——— Begin Update B Part 2 of 2 ———

Siemens has released updates for TIA Portal v15 and v16 and is working on updates for TIA Portal v14. Siemens recommends specific countermeasures as there are currently no fixes available for the latter.
Siemens recommends installing the following software update to address this vulnerability:

——— End Update B Part 2 of 2 ———

Siemens has identified the following specific workarounds and mitigations users can apply to reduce the risk:

  • Remove write permissions for every non-administrative user on files and folders located below the “TraceEngine” folder (usually located at “C:\ProgramData\Siemens\Automation”).

As a general security measure, Siemens strongly recommends users protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends users configure the environment according to Siemens’ operational guidelines for Industrial Security, and follow the recommendations in the product manuals.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on us-cert.cisa.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.cisa.gov in the Technical Information Paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.

No known public exploits specifically target this vulnerability. This vulnerability is not exploitable remotely.

Source:

https://us-cert.cisa.gov/ics/advisories/icsa-20-014-05